Siemens SINAMICS Fault F01001 — Overcurrent

Fault Code Siemens SINAMICS G120 / S120 Siemens

What This Fault Means

F01001 indicates the drive's output current exceeded the hardware overcurrent limit. The Control Unit shuts down the pulse pattern immediately to protect the IGBTs.

Common Causes

Recommended Fix

  1. Disconnect the motor cables from U, V, W terminals and megger-test.
  2. If motor and cables pass, re-run motor identification (P1910 = 1, commission).
  3. Increase the ramp-up time (P1120).
  4. Check for ground faults in the cable run.
  5. If F01001 persists with no motor connected, the power module needs replacement.