Siemens SINAMICS Fault F07011 — Motor Overtemperature

Fault Code Siemens SINAMICS G120 / S120 Siemens

What This Fault Means

F07011 indicates the motor temperature calculated by the drive's I²t thermal model (or measured by a PTC/KTY sensor) exceeded the warning/trip threshold. The drive shuts down to prevent motor insulation damage.

Common Causes

Recommended Fix

  1. Check the motor temperature using an IR thermometer — compare to motor nameplate max temp.
  2. Verify the external cooling fan is running (common failure on 1LA7 motors).
  3. Check drive parameters P0335 (motor cooling type) and P0340 (motor thermal time constant) match the motor.
  4. If using a PTC/KTY sensor, measure the sensor resistance — PTC should read <1.5kΩ when cool.
  5. Reduce the load or duty cycle if the motor is genuinely overheating.