PowerFlex Fault F002 — Auxiliary Input

Fault Code PowerFlex 525 / 753 / 755 Allen-Bradley

What This Fault Means

F002 indicates an external fault signal was received on one of the drive's digital inputs configured as a fault input. This is typically wired to an external safety device or overload relay.

Common Causes

Recommended Fix

  1. Identify which digital input is configured as the auxiliary fault (check Parameter 361–366 on PF525).
  2. Trace the wiring back to the external device.
  3. Reset the external device (overload relay, E-stop) if the condition has cleared.
  4. Verify 24VDC is present at the digital input when the external device is in the run-permissive state.
  5. If the wiring checks out and the external device is healthy, check for a loose terminal or broken wire.