F30001 — Power unit: Overcurrent

On a Siemens SINAMICS G120, fault F30001 reads “Power unit: Overcurrent”. Here's what to check — cited to the manual.

Grounded · SINAMICS G120C List Manual (LH13, 04/2014, A5E33840768B AA) · manual-cited
What this fault means
The power unit has detected an overcurrent condition.
SINAMICS G120C List Manual (LH13, 04/2014, A5E33840768B AA), p.522
“F30001 Power unit: Overcurrent — Cause: The power unit has detected an overcurrent condition.”

First checks (from manual)

  • check the motor data - if required, carry out commissioning
  • check the motor circuit configuration (star/delta)
  • U/f operation: Increase up ramp
  • U/f operation: Check assignment of rated currents of motor and power unit
  • check the line supply quality
  • Reduce motor load
  • Correct connection of line reactor
  • check the power cable connections
  • check the power cables for short-circuit or ground fault
  • check the length of the power cables
  • replace power unit
  • check the line supply phases
SINAMICS G120C List Manual (LH13, 04/2014, A5E33840768B AA), p.522 — Remedy column