Rockwell Automation PowerFlex 525 · Parameter t097
t097 — Anlg In mA Loss
Sets the response to a loss of input. When the 4…20 mA input is used for any reference, any input less than 2 mA is reported as a signal loss. Input must exceed 3 mA for the signal loss condition to end. If enabled, this function affects any input that is being used as a speed reference or PID reference or PID setpoint in the drive. Options 4 “Min Freq Ref”
Grounded · PowerFlex 525 Adjustable Frequency AC Drive User Manual (520-UM001O-EN-E) · manual-cited
Cited reference
t097
Anlg In mA Loss
Sets the response to a loss of input. When the 4…20 mA input is used for any reference, any input less than 2 mA is reported as a signal loss. Input must exceed 3 mA for the signal loss condition to end. If enabled, this function affects any input that is being used as a speed reference or PID reference or PID setpoint in the drive. Options 4 “Min Freq Ref”
PowerFlex 525 Adjustable Frequency AC Drive User Manual (520-UM001O-EN-E), p.100
“t097 [Anlg In mA Loss] Related Parameters: P043, P044, A426, A427”