t094 — Anlg In V Loss

Sets the response to a loss of input. When the 0…10V input (or –10…+10V) is used for any reference, any input less than 1V is reported as a signal loss. Input must exceed 1.5V for the signal loss condition to end. If enabled, this function affects any input that is being used as a speed reference, PID reference or PID setpoint in the drive. Options 4 “Min Freq Ref”

Grounded · PowerFlex 525 Adjustable Frequency AC Drive User Manual (520-UM001O-EN-E) · manual-cited

Cited reference

t094
Anlg In V Loss
Sets the response to a loss of input. When the 0…10V input (or –10…+10V) is used for any reference, any input less than 1V is reported as a signal loss. Input must exceed 1.5V for the signal loss condition to end. If enabled, this function affects any input that is being used as a speed reference, PID reference or PID setpoint in the drive. Options 4 “Min Freq Ref”
PowerFlex 525 Adjustable Frequency AC Drive User Manual (520-UM001O-EN-E), p.99
“t094 [Anlg In V Loss] Related Parameters: P043, P044, A426, A427”