F007 — Motor Overload

On a Rockwell Automation PowerFlex 40, fault F007 reads “Motor Overload”. Here's what to check — cited to the manual.

Grounded · PowerFlex 40 Adjustable Frequency AC Drive User Manual (22B-UM001J-EN-E) · manual-cited

Parameters to check

P033
Motor OL Current
Set to the maximum allowable motor current. The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60 seconds.
PowerFlex 40 Adjustable Frequency AC Drive User Manual (22B-UM001J-EN-E), p.53
“P033 [Motor OL Current] Related Parameters: A055, A058, A061, A089, A090,”

Full P033 reference →